Menu
linkedin youtube GET A QUOTE

Home / Products / Evaporators / TX-TXC Multi-Circuit Glycol

Standard Refrigeration
TXC Multiple Purpose
ChillerOptimized for
40% Glycol Mix

TXC-MPG chiller barrels have been optimized for 40% Glycol mixes, offering added protection for colder climate locations. Ideal for system builder and OEM replacement units. They are designed to work with higher pressure refrigerants.

TXC-MPG chiller barrels have been optimized for 40% Glycol mixes, offering added protection for colder climate locations. Ideal for system builder and OEM replacement units. They are designed to work with higher pressure refrigerants.

Standard Designs
TXC dual and multiple circuit chillers are available in standard designs for fresh water duty. They are available in 10 catalog models from 30 to 200 tons. ¾” Insulation is fitted as standard (for 1½” thick insulation order TXC-GLT).

Tube Materials
TX chillers are manufactured with enhanced ¼” diameter copper tubing and TXC utilize enhanced ⅜” OD copper tubing.

Customization
Configurable and custom vessels are available with special materials of construction as required by you or your client.

Options
Units are available with left, right or top mounted shell side connections, please specify at time of order. As standard ¾” insulation is included, 1½” or no insulation is also available.

Alternative Options
For lower temperature applications, please use TXC-GLT (same dimensions as MPG units, but with thicker insulation).

 

Click on image to zoom

*Ratings are based on entering water 54°F, leaving water 44°F, saturated suction temperature of 35°F, entering TXV temperature of 100°F with 7°F of superheating
Dimensions do not include the 3/4″ insulation
Shell side nozzle are available in right (R), left (L) or top (T) orientations, R is the standard default
ProSuite software values are the most accurate
Includes ¾” thick insulation as standard
Values shown are correct at the time of publication, all data should be reconfirmed at the time of purchase
Capacity Tons = 12,000 BTU/hr

Click on image to zoom

Values shown are correct at the time of publication, all data should be reconfirmed at the time of purchase